Sr. No. Parameters Specification
1 Product category / description EMI/RFI Filter
2 Mounting Chassis mounting
3 Filter category Three phase without neutral & three phase without neutral with surge suppressor
Electrical characteristics
Sr. No. Parameters Specification
1 V/A rating 500 Amp,550 Amp & 600 Amp, 440VAC(P-P) 50/60Hz
2 Insulation resistance at 500 VDC for 60 sec ± 5 sec. (by shorting L & N terminals & w.r.t. earth) Min. 300MΩ
3 H.V. break down test for 60 sec ± 5 sec. (by shorting L & N terminals & w.r.t. earth) 1.5 KVAC
4 MTBF@40°c/230V(Mil-HB-217F) 200,000 hours
Operating / functional characteristics
Sr. No. Parameters Specification
1 Operating temp. range 40°c/-25° +85°c
2 Input terminals (standard) Busbar terminals
3 Output terminals (standard) Busbar terminals
4 Size (L-700 x W-370 x H-250) in mm.
5 Material CRCA 1.2 mm thickness
6 Body In fabricated CRCA metal can with nickel plating
7 Current carrying parts Cu alloy, tin/nickel plating
Reference standards
Sr. No. Parameters Specification
1 Reference standard EN60939-3:2015 & EN60939-2:2005, CSA C22.2 NO. 8-13, UL 1283 (5th Edition)
Safety approvals
Sr. No. Parameters Specification
1 CE marking Yes
2 cCSAus Yes

Annexure

Standard Variety

Standard variety

Sr. No. With reference to Available option RoHS / Non RoHS Safety approvals & / or markings
1 EMI/RFI Filter

Filter EMI/RFI three phase three wire, 440(P-P)VAC, with/without surge suppressor, chassis mounting in fabricated metal can. (without neutral)

Other customized options available on request , subject to MOQ & commercial acceptance.

Sr. No. With reference to Available option RoHS / Non RoHS Safety approvals & / or markings
1 Product category
  • EMI/RFI Filter
  • EMI/RFI Filter with surge suppressor
  • EMI/RFI Filter with special features
2 Connection terminals
  • Busbar terminals
    3 Flammability corresponding
    • UL 94 V-2 or better
    4 Operating voltage
    • Three phase three wire (P-P) 440 Vac
    5 Operating frequency
    • 50/60Hz
    6 Design corresponding to
    • EN60939-3:2015 & EN60939-2:2005
    • CSA C22.2 NO. 8-13
    • UL 1283 (5th Edition)
    7 Mounting
    • Chassis mounting