Specification

Parameter
Sr. No. Parameters Specification
1 Product category / description RFI/EMI Filter
2 Mounting Chassis mounting
3 Filter category Three phase without neutral & three phase without neutral with surge suppressor
Electrical characteristics
Sr. No. Parameters Specification
1 V/A rating 3 Amp, 6 Amp, 10 Amp,15 Amp, 20 Amp, 30 Amp & 40 Amp, 440VAC (P-P) 50 / 60Hz
2 Insulation resistance at 500 VDC for 60 sec ± 5 sec. (by shorting L & N terminals & w.r.t. earth) Min. 300MΩ
3 H.V.break down test for 60 sec ± 5 sec. (by shorting L & N terminals & w.r.t. earth) 1.5 KVAC
4 MTBF@40°c/230V(Mil-HB-217F) 400,000 hours
Operating / functional characteristics
Sr. No. Parameters Specification
1 Operating temp. range 40°c/-25° +85°c
2 Input terminals (standard) Touch safe terminals
3 Output terminals (standard) Touch safe terminals
4 Size (L-140 x W-110 x H-40) in mm.
5 Material CRCA 0.7 mm thickness
6 Body In fabricated CRCA metal can with nickel plating
7 Current carrying parts Cu alloy, tin/nickel plating
Reference standards
Sr. No. Parameters Specification
1 Reference standard IEC-60939-1 & 2, CSA C22.2 NO. 8-13 & UL 1283 (5th Edition)
Safety approvals
Sr. No. Parameters Specification
1 CE marking Yes
2 cCSAus Yes

Annexure

Standard Variety

Standard Variety

Sr.no. With Reference To Available Option RoHS / Non RoHS Safety Approvals & / or Markings
1 RFI/EMI Filter

Filter RFI/EMI three phase three wire, 440(P-P)VAC, with/without surge suppressor, chassis mounting in fabricated metal can. (without neutral)

Other customized options available on request , subject to MOQ & commercial acceptance.

Sr.no. With Reference To Available Option RoHS / Non RoHS Safety Approvals & / or Markings
1 Product category
  • RFI/EMI Filter
  • RFI/EMI Filter with surge suppressor
  • RFI/EMI Filter with special features
2 Connection terminals
  • Touch safe terminals
  • Screw terminals
  • Bus-bar terminals
  • Wire lead terminals
3 Flammability corresponding
  • UL 94 V-2 or better
4 Operating voltage
  • Three phase three wire (P-P) 440 Vac
5 Operating frequency
  • 50/60 Hz
6 Design corresponding to
  • IEC-60939-1 & 2
  • CSA C22.2 NO. 8-13
  • UL 1283 (5th Edition)
7 Mounting
  • Chassis mounting

Download PDF