Features
- NEMA Receptacles are available in wide range of current & Voltage ratings
- Wide range of mounting styles and terminals to suit various design requirements
- Components available according to UL and NEMA standards
- Wide range of operating temperature - up to 125 Deg Centigrade
- All the safety approvals are available for any colour.
Drawings
Specification
Electrical Characteristics
Sr. No. | Parameters | Specification |
---|---|---|
1 | Product Category / Description | NEMA Receptacle |
2 | Type / Sub Type | Straight Blade |
3 | NEMA Type | 5-20R Type |
4 | V/A Rating | 125V 20A |
5 | Insulation Resistance at 500 VDC | 100 M ohms Min. |
6 | H.V.Break Down Test (For 1-Minute) | 2 KVAC |
7 | Contact Resistance (Initial) | 10 m ohms Max |
Operating / Functional Characteristics
Sr. No. | Parameters | Specification |
---|---|---|
1 | Mounting | Panel, Snap mounting |
2 | Panel Thickness | 1.00-2.00mm |
3 | Terminals | 6.30 x 0.80 |
4 | Withdrawal force in kg | 1.3 to 6.7 kg |
5 | Permissible Temp. With/Without Load | 0°C TO 65°C * on request upto 125°C |
6 | Permissible Temp. For Soldering | 270°C for 5 Sec. Max. |
Material
Sr. No. | Parameters | Specification |
---|---|---|
1 | Body, Cover | Nylon-6, GF20%, V-2 |
2 | Color (Standard) | Black |
3 | Current Carrying Parts | Cu Alloy, Tin Plating |
Reference Standards / Safety Approvals
Sr. No. | Parameters | Specification |
---|---|---|
1 | Reference Standard | UL-498, NEMA WD 6:2002, CAN / CSA C22.2 No. 42-99 |
2 | Safety Approvals | cULus |